Medium Voltage Distribution Protection: Explore Transformer Protection Systems

Medium Voltage Distribution Protection

In the world of electrical engineering, protecting medium voltage distribution systems—particularly transformers—represents one of the most critical yet complex challenges facing building services engineers. While transformers are inherently reliable devices with proven track records of decades-long service, the consequences of unprotected faults can be catastrophic, making proper protection design essential.

The key to effective protection lies in understanding that simplicity often trumps complexity. Engineers, especially those working with smaller transformers or remote installations, should resist the temptation to over-engineer protection schemes. Additional relays increase the risk of nuisance tripping, and most protection devices can only respond after a fault occurs—they cannot predict impending failures.

The Foundation: Understanding Earth-Fault Protection

Why Separate Earth-Fault Protection Matters

A common question among engineers is why earth-fault protection cannot simply rely on three-phase short-circuit protection. The answer lies in fault current magnitude. While three-phase protection can handle earth faults when currents are sufficiently high, many earth-fault scenarios produce currents too low for reliable detection by standard overcurrent relays.

The Challenge of Neutral Earthing Resistors (NER)

The electrical path to earth through ground itself is notoriously poor, with significant resistance that varies by location and soil conditions. In distribution networks, the primary earth return path typically runs through 11 kV cable armor or sheath. Over extended distances, this path’s resistance becomes substantial, creating voltage differences between locations during fault conditions.

Consider a practical example: A 10 MVA, 33/11 kV distribution transformer with 9% impedance (approximately 1Ω) connected via 300mm² XLPE/SWA cable experiences the following conditions during an earth fault:

  • Cable impedance: R₁ = 0.0601 Ω/km, X₁ = 0.091 Ω/km
  • Earth fault current: Limited by total circuit impedance
  • Voltage rise: Can exceed safe limits without proper control

To maintain earth voltage rise below 430V—the typical safety threshold—engineers commonly employ neutral earthing resistors (NERs) on 33 kV, 11 kV, and 6.6 kV systems. These resistors limit fault current to manageable levels, typically matching the transformer’s full-load current.

However, this current limitation creates a protection challenge. For a 2 MVA transformer with an overcurrent relay set at 180A (allowing 50% overload), an earth-fault current of 1000A provides only 5.5 times the setting current, resulting in operating times of 4-5 seconds—potentially too slow for adequate protection.

Advanced Protection Strategies

Balanced Earth-Fault (BEF) Protection

Balanced earth-fault protection exploits the characteristics of delta-star connected transformers. When an earth fault occurs on the secondary side, the primary currents maintain their zero vector sum, meaning a balanced current transformer connection on the primary side shows zero output. Only primary winding earth faults produce current in the relay circuit.

Key Implementation Points:

  • Relay settings: Typically 10-40% of full-load current
  • Sensitivity considerations: Must account for magnetization current imbalances and harmonic distortion
  • Stability requirements: A 20% setting provides a good compromise between sensitivity and stability
  • Time grading: Requires 200% of normal phase-fault grading margins due to CT ratio errors

Restricted Earth-Fault (REF) Protection

REF protection adds sophistication by incorporating a current transformer in the main earth-to-neutral connection, restricting protection to the transformer’s secondary winding. This approach offers several advantages:

  • Zone selectivity: Operates only for faults within the protected zone
  • High sensitivity: Maintains effectiveness even for faults near the neutral point
  • Solid earthing compatibility: Works well with 400/230V systems where neutrals are solidly earthed

Typical REF settings range from 30% to 40% of full-load current, providing adequate sensitivity while maintaining stability against harmonic-rich loads and CT mismatches.

 

Standby Earth-Fault (SBEF) Protection

Originally developed to protect neutral earthing resistors, SBEF relays serve as a “last line of defense” for low-voltage systems. With only 230V to earth, even small impedances can limit fault currents below the operating threshold of standard protective devices.

SBEF relays use a very inverse characteristic but operate more slowly than standard relays, with settings typically around 20% of phase current. The key is positioning the relay characteristic between fuse curves—discriminating with 100A fuses but not 125A fuses.

Optimizing Response Times

High-Set Instantaneous Overcurrent (HSOC) Protection

Standard inverse relays protecting transformers can be frustratingly slow, taking several seconds to respond to medium voltage faults while maintaining discrimination with downstream devices. HSOC protection addresses this by exploiting the dramatic difference in fault currents between primary and secondary faults.

Design Approach:

  1. Calculate maximum secondary fault current: Determines the threshold above which faults must be primary-side
  2. Add safety margin: Typically 30% to account for CT errors and variations
  3. Set instantaneous element: Just above this threshold for immediate operation

For a 1 MVA transformer example:

  • Maximum secondary-referred primary current: 1050A
  • HSOC setting: 1050A × 1.3 = 1365A
  • Result: Primary faults clear in 0.05 seconds instead of 1.7 seconds

The Very Inverse Alternative

Modern protection design often favors very inverse (VI) relay characteristics over the traditional standard inverse plus HSOC combination. VI relays provide inherently fast operation at high currents while maintaining proper discrimination at lower fault levels, often eliminating the need for separate instantaneous elements.

Specialized Protection: The Buchholz Relay

For oil-filled transformers, the Buchholz relay represents a unique early-warning capability. Unlike other protection devices that respond to fault effects, Buchholz relays detect fault precursors through gas analysis.

Operating Principles:

  • Upper float: Detects gradual gas accumulation from minor faults (inter-turn faults)
  • Lower float: Responds to violent oil movement from major internal faults
  • Dual function: Provides both alarm and trip capabilities

Installation requires an oil conservator system, with the relay positioned in the connecting pipe. While historically common, the shift toward resin-cast transformers has reduced Buchholz relay applications, now primarily limited to transformers rated 2 MVA and above.

Design Philosophy and Best Practices

The Simplicity Principle

A successful protection design strikes a balance between comprehensive coverage and operational reliability. Key considerations include:

  • Proven reliability: Transformers typically provide decades of trouble-free service
  • Nuisance tripping risks: Additional complexity increases unwanted operations
  • Maintenance requirements: Complex schemes demand more sophisticated maintenance programs
  • Site accessibility: Remote locations favor simpler, more robust protection

Setting Philosophy

Protection relay settings require a careful balance between sensitivity and stability:

  • Too sensitive: Increases nuisance tripping from load imbalances and harmonics
  • Too conservative: May fail to detect genuine fault conditions
  • Typical compromises: 20% for BEF, 30-40% for REF, based on system characteristics

Future-Proofing Considerations

Modern digital relays offer extensive built-in characteristics and instantaneous elements, making protection scheme modifications straightforward. However, the fundamental principles of proper coordination and appropriate settings remain unchanged regardless of relay technology.

Conclusion

Effective medium voltage distribution protection requires understanding both the theoretical principles and practical limitations of protection systems. While the array of available protection types might seem overwhelming, successful designs focus on matching protection complexity to system requirements.

The most reliable protection schemes combine appropriate sensitivity with operational stability, recognizing that the primary goal is preventing damage while minimizing service interruptions. Whether dealing with earth-fault detection, instantaneous overcurrent protection, or specialized devices like Buchholz relays, the key lies in understanding each system’s role within the broader protection philosophy.

As distribution systems continue evolving, these fundamental protection principles remain constant, even as the technology implementing them advances. Engineers who master these concepts will be well-equipped to design protection systems that reliably serve their intended purpose for decades to come.

Related Post

Island Mode Operation: Critical Protection Challenges in Distributed Networks
Read More
Symmetric and Asymmetric Fault Currents: Why the X/R ratio determines everything from arc energy to switchgear selection
Read More
Understanding Fault Current Contributions
Read More
Unit and Differential Protection for Medium Voltage Distribution Systems
Read More
Understanding ANSI Device Numbering in Medium Voltage Distribution Systems
Read More
Generator Protection in Medium Voltage Distribution Systems
Read More
Protection System Coordination: Mastering Grading Margins and Relay Characteristics
Read More
Protection Relays: The Intelligence Behind Medium Voltage System Safety
Read More
Current and Voltage Transformers in Medium Voltage Protection Systems
Read More
Medium Voltage Distribution Protection: Essential Systems and Components
Read More

Get a free calculation
of your saving and join the evolution

Fill out the form, and let us demonstrate how our expertise and accreditation ensure reliable connection solutions. Our team will reach out to provide tailored advice for your electricity connection project.
Lead Form
Paragon Energy Networks
We at Paragon Energy Networks are a specialist Independent Connection Provider (ICP), we compete with the incumbent Distribution Network Operators (DNO’s) to complete your LV and HV electricity connection activities.
Recent News & Insights

Copyright © 2025 Paragon Energy Networks Ltd. All Rights Reserved. This website, including its design, text, graphics, logos, and other original content, is the exclusive property of Paragon Energy Networks unless otherwise stated. All materials are protected by copyright, trademark, and other intellectual property laws.


apartmentenvelopephone-handsetcrossmenuchevron-right linkedin facebook pinterest youtube rss twitter instagram facebook-blank rss-blank linkedin-blank pinterest youtube twitter instagram